RZN 4503-T Smoke and Natural Ventilation Control Panel

Compact smoke and natural ventilation control panel providing 3 A actuator capacity, one monitored fire line, one ventilation group and integrated local controls.

  • Primary application: Compact smoke ventilation systems, particularly stairwells
  • Total output: 24 V DC / 3 A
  • Configuration: 1 monitored fire line / 1 ventilation group
  • Local controls: Integrated smoke-vent and ventilation buttons
  • Interfaces: Two programmable volt-free signalling contacts
  • Weather control: Direct connection for a compatible rain sensor or wind and rain sensor
  • Standby operation: Monitored battery-backed operation
  • Housing: Compact aluminium enclosure, IP30
       

Manufactured By: D+H Mechatronic D+H Mechatronic

DOWNLOADS
Category:

Compact smoke and natural ventilation control panel

The D+H RZN 4503-T is a compact smoke and natural ventilation control panel developed particularly for stairwells and smaller smoke ventilation systems.

It provides 24 V DC output with up to 3 A total actuator capacity, one monitored fire line and one ventilation group within a compact aluminium enclosure.

The front of the panel incorporates smoke-vent and natural ventilation controls, allowing the panel to provide local operation without requiring a separate ventilation switch for basic use.

Typical applications

  • Stairwell smoke ventilation
  • Small smoke-relief systems
  • Automated windows, louvres and rooflights
  • Single-zone smoke-control systems
  • Combined smoke control and day-to-day natural ventilation
  • Projects requiring compact local control and indication
  • Natural ventilation systems requiring battery-backed operation

Key features

  • 24 V DC stabilised output
  • 3 A total drive current
  • One monitored fire line
  • One ventilation group
  • Integrated smoke-vent operating button
  • Integrated natural ventilation controls
  • Monitored standby battery operation
  • Two freely programmable volt-free signalling contacts
  • Direct connection for a compatible rain sensor
  • Direct connection for a compatible wind and rain sensor
  • Switchable smoke-control safety functions
  • Compact aluminium enclosure
  • Separate mounting plate and upper housing for installation access

Available enclosure colours

Model Enclosure colour Article number
RZN 4503-T Orange, approximately RAL 2011 30.107.30
RZN 4503-T/G Grey, approximately RAL 7035 30.107.40
RZN 4503-T/Y Yellow, approximately RAL 1004 30.107.60

Technical information

Product type Compact smoke and natural ventilation control panel
Primary application Stairwell and small smoke ventilation systems
Mains supply 230 V AC / 50 Hz / 100 VA
Standby consumption Less than 5 W
Panel output 24 V DC / 3 A total drive current
Output ripple Less than 0.5 Vss
Fire lines 1 monitored fire line
Ventilation groups 1
Signalling contacts 2 freely programmable volt-free contacts
Local controls Integrated smoke-vent and natural ventilation buttons
Weather-sensor connection Compatible rain sensor or wind and rain sensor without an additional module
Standby operation Monitored battery-backed operation
Battery arrangement One Type 8 battery
Operating duty Continuous monitoring; alarm and ventilation operation at 30% short-time duty
Protection rating IP30
Operating temperature −5°C to +40°C
Housing Aluminium
Dimensions 156 × 235 × 82 mm
Panel weight 1.9 kg excluding project packaging and accessories
Manufacturer D+H Mechatronic

Smoke-control operation

The RZN 4503-T receives a fire or smoke-control signal through its monitored fire line.

When an alarm signal is received, the panel gives priority to the fire-mode sequence and commands the connected windows, louvres or roof openings to move to their required smoke-control position.

Switchable safety functions include fault-equals-alarm operation and smoke-control retriggering. These functions are selected to suit the approved project sequence.

Integrated local controls

The front of the RZN 4503-T incorporates smoke-vent and natural ventilation operating controls.

This compact arrangement is particularly useful in stairwells and smaller systems where local operation and indication are required at the panel position.

Additional compatible smoke-vent operating panels may be connected where remote manual control is required.

Natural ventilation operation

The panel can operate connected openings for normal day-to-day ventilation while retaining fire-mode priority.

Compatible natural ventilation controls may include:

  • the integrated ventilation buttons;
  • compatible remote ventilation switches;
  • a rain sensor;
  • a wind and rain sensor;
  • low-level external control contacts; and
  • other approved project interfaces.

Weather-sensor connection

A compatible rain sensor or wind and rain sensor can be connected directly to the RZN 4503-T without an additional weather interface module.

During normal ventilation operation, the weather signal can command connected openings to close when rain or excessive wind is detected.

Fire-mode commands retain priority over normal weather-related ventilation control.

Programmable signalling contacts

The RZN 4503-T provides two freely programmable volt-free signalling contacts.

These contacts may be configured for defined project functions such as status, alarm or fault indication, subject to the selected panel configuration and interface requirements.

They can support low-level coordination with a BMS or other compatible building system where suitable volt-free contacts are required.

Standby batteries and mains power failure

The RZN 4503-T is supplied with monitored standby battery capacity to maintain control-system operation if the normal 230 V AC mains supply fails.

Where automatic close on loss of mains power forms part of the operating sequence, the panel can command the connected openings to close while remaining available for a subsequent fire signal.

Battery selection and standby performance must be confirmed against the connected actuator load, operating sequence and project requirements.

Drive capacity and system selection

The 3 A output capacity must be checked against:

  • the selected actuator models;
  • the rated and starting current of each actuator;
  • the number of connected actuators;
  • simultaneous operation;
  • cable length and voltage drop;
  • the required fire-mode position;
  • natural ventilation controls;
  • external signalling requirements; and
  • the approved cause-and-effect sequence.

Installation and access

The RZN 4503-T uses a separate mounting plate and upper enclosure, supporting accessible installation and termination.

The panel location should provide:

  • suitable structural fixing;
  • a dedicated 230 V AC supply;
  • clear actuator and control-cable routes;
  • access for testing and commissioning;
  • access for battery replacement; and
  • future maintenance access.

System coordination

The panel is selected and configured together with the automated openings, actuator loads, field cabling, fire interfaces, natural ventilation controls, standby power and approved cause-and-effect sequence.

EBSA works with the project team to coordinate these elements with the fire strategy and relevant design requirements.

Compare smoke control panels


Compare the RZN 4503-T with CPS-B, RZN, CPS-P and CPS-M smoke control panels

Inspection, testing and maintenance

EBSA provides inspection, functional testing, fault diagnosis, repairs and planned maintenance for new and existing D+H smoke and natural ventilation systems throughout New Zealand.

EBSA technical support

EBSA can assist with actuator selection, connected-load calculations, panel configuration, fire and ventilation interfaces, weather controls, field-cabling coordination, commissioning support and ongoing maintenance.